Shenzhen Kinda Technology Co., Ltd

Shenzhen Kinda Technology Co., Ltd

Manufacturer from China
Active Member
7 Years
Home / Products / Variable Frequency Drive Pump Control /

Residential Vfd Pump Drive , Water Supply Pump Inverter Drive Energy Saving

Contact Now
Shenzhen Kinda Technology Co., Ltd
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MrTim
Contact Now

Residential Vfd Pump Drive , Water Supply Pump Inverter Drive Energy Saving

Ask Latest Price
Video Channel
Place of Origin :China
Brand Name :Kinda
Model Number :KD386
MOQ :Negotiable
Price :Negotiable
Delivery Time :3~8 Day
Payment Terms :TT
Supply Ability :Adequate inventory
control :Main/slave control energy saving
installation :Simple wiring installation
PCB protection :Spray three anti-paint to protect the circuit board intelligently and efficiently
design :Modular design, compact structure, easy maintenance and enhanced product interchangeability
start up :Simple parameter setting, one-button start automatic addition and subtraction pump control
run :Smooth main/slave switching, no change in water pressure
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Residential Area Variable Frequency Drive Pump Control Water supply

When the water supply automatic control system is working, when the water consumption is changed by the high sensitivity pressure sensor installed on the water supply pipe network, the device detects the pressure change of the water supply pipe network. When the pressure of the pressure transmitter is the largest, the frequency of the inverter is the lowest, the minimum speed of the pump motor. When the pressure of the pressure transmitter is the smallest, the frequency of the inverter is the highest, the speed of the pump motor is the highest, and the frequency of the inverter changes with the water consumption. And change.

After the microcomputer judges the calculation and compares it to the set pressure, it sends a command to change the frequency to the controller. By changing the frequency, the controller automatically adjusts the peak and valley water consumption to ensure that the water supply network pressure is constant, changing the speed of the pump motor and the number of pumps activated.
Constant pressure water supply inverters are widely used in residential, hotel, agricultural constant water pressure stabilization products.

Residential Vfd Pump Drive , Water Supply Pump Inverter Drive Energy Saving

Function code Default value Set value Description
F1-11 1 I# inverter 1 1# inverter (master), it must connect the pressure sensor.
2# inverter 2 2# inverter (slave / standby master), connect the pressure senor.
3# inverter 3 3# and 4# inverters (slave).
4# inverter 4 Warning: the address of each inverter cannot be the same, otherwise, the system will work abnormally.
F0-00 1 2 Multiple pumps system
F0-01 0.4MPa Customer set 1. Please set it correctly based on requested pressure, the unit is MPa, 1MPa=10bar.
2. Most of the family used systems, the pressure is 0.3~0.4MPa (3~4bar)
F0-02 80% Customer set Wake up pressure; it is the percentage of F0-01.
F0-03 0 0 It must be set as “0” while use 0~10V remote pressure gauge.
1 It must be set as “1” while use 4~20mA pressure transducer.
F0-04 1.6MPa 1.6MPa 1. To set the maximum measure range of pressure transducer.
2. It must be set correctly, otherwise it may cause pressure is inaccurate.
F0-25 300Min Customer set To set the running time as master pump, when time arrive, it switches to next pump as master.
When set F0-25=0, this pump will only work as slave pump.